Steam Chiller Performance Curves

Performance Curves ​

The same as packaged DFA chiller. Please refer to Performance Curves for details.

Copy

Coefficient of Performance (COP)

Rated COP: 1.50 — IPLV COP: 1.72

LoadCOPFactorResult
100%1.50.010.015
75%1.7310.420.727
50%1.7930.450.807
25%1.4320.120.172

The integrated part load value (IPLV) reflects chiller's actual COP in operation.

Calculated per AHRI560.

Copy

Operating Noise dB(A)

Model BSY20~5075~200≥250
Steam chiller≤52≤53≤53
Pumpset≤57≤57≤59
Cooling tower≤62≤64≤66
Outside enclosure≤40≤41≤42
Zoom
Copy

Nomenclature

BSY200XII0.8-FaHigh pressure typeSteam inlet gauge pressure: 0.8 MPaGeneration code (XII indicates 12)Cooling capacity: 10Packaged chillerChiller type: S (steam type)BROAD

Model Selection & Ordering ​

Steam selection ​

  • Please specify saturated steam pressure and temperature.
  • The temperature of overheated steam should be ≤180°C (except special order).

Other factors ​

Load, quantity, flow, pressure, split shipment, control, machine room, location, ordering and warranty are the same as those of packaged direct-fired chillers. Please refer to Model Selection & Ordering for details.

Supply list ​

Refer to packaged DFA supply list on Supply List.