DFA Performance Curves
Zoom
Copy
Packaged DFA Performance Curves
Electricity consumption means the consumption of the chiller and pumpset.
Copy
Coefficient of Performance (COP)
Rated COP: 1.42, IPLV COP: 1.63
| Load, % | COP | Factor | Result |
|---|---|---|---|
| 100 | 1.42 | 0.01 | 0.014 |
| 75 | 1.638 | 0.42 | 0.688 |
| 50 | 1.692 | 0.45 | 0.761 |
| 25 | 1.372 | 0.12 | 0.165 |
The integrated part load value (IPLV) reflects chiller’s actual COP in operation.
Calculated per AHRl560.
Copy
Operating Noise dB (A)
| Model BZY | 20~50 | 75~200 | ≥ 250 |
|---|---|---|---|
| DFA | <57 | <58 | <60 |
| pumpset | <57 | <57 | <59 |
| cooling tower | <62 | <64 | <66 |
| outside enclosure | <42 | <43 | <44 |
Emissions:
- Standard GB 13271-2014.
- NOx≤46ppm(O₂=3.5%).
- Special order equipped with low NOx burner and electrostatic cleaner on exhaust port, and emission is almost zero.
- Exhaust heat recovery technology can realize the "elimination of white smoke" in cold area.
Zoom
Copy
Nomenclature
*Fuel types: B — oil, C — LPG, D — natural gas, E — town gas.