Packaged Hot W. / Exhaust Chiller Rated Parameters

Copy

Packaged Hot W. / Exhaust Chiller Rated Parameters

BHY/BEY: hot water / exhaust from power generation or industrial waste streams (pumpset, enclosure data are the same as steam chiller)

Code / ModelUnit203050751001251502002503004005006008001000
BH: Cooling / Heating capacity
Cooling capacitykW233349582872116314541745232629083489465258156978930411630
Heating capacitykW///////////////
BH: Chilled W.
Chilled W. flow ratem³/h28.642.971.410714317921428635742957171485711431429
Chilled W. Pressure dropkPa303030303040404050506060606060
BH: Cooling W.
Cooling W. flow ratem³/h47.571.21191782382973574765957149521189142719032379
Cooling W. Pressure dropkPa505050505050505080808090909090
BH: Heating W.
Heating W. flow ratem³/h///////////////
Heating W. Pressure dropkPa///////////////
BH: Hot W.
Hot W. Con-sumptionm³/h9.41423.535.246.958.770.593.9117.4140.9188234.9281.8375.9469.9
BH: Exhaust consumption
Exhaust Consaption (cooling)kg/h///////////////
Exhaust Consaption (heating)kg/h///////////////
BH: Misc.
Power demandkW2.13.23.23.65.35.36.48.68.912.412.415.818.820.826.3
Solu-tion Wt.t0.71.11.422.83.64.85.67.38.510.91416.92125.5
Unit ship. Wt.t4.25.87.511.412.915.218.122.426.8//////
Main shell Wt.t2.444.75.25.96.98.111.613.416.117.821.923.829.241.5
Chiller opera- tion Wt.t4.96.78.713.215.117.821.125.931.438.64758.964.782.599
BE: Cooling / Heating capacity
Cooling capacitykW233349582872116314541745232629083489465258156978930411630
Heating capacitykW153230384575767959115115341918230130683835460261377671
BE: Chilled W.
Chilled W. flow ratem³/h28.642.971.410714317921428635742957171485711431429
Chilled W. Pressure dropkPa303030303040404050506060606060
BE: Cooling W.
Cooling W. flow ratem³/h47.571.21191782382973574765957149521189142719032379
Cooling W. Pressure dropkPa505050505050505080808090909090
BE: Heating W.
Heating W. flow ratem³/h13.119.632.74965.481.898131163196262327394523654
Heating W. Pressure dropkPa202020202020203030404050506060
BE: Hot W.
Hot W. Con-sumptionm³/h///////////////
BE: Exhaust consumption
Exhaust Consaption (cooling)kg/h144021583606541472159025108321443918057216632890236115433325780072246
Exhaust Consaption (heating)kg/h153022893819572276389553114451529919036228903059838189460146107976378
BE: Misc.
Power demandkW2.13.23.23.65.35.36.48.68.912.412.415.818.820.826.3
Solu-tion Wt.t1.11.72.43.5456.589.211.51519.6232731
Unit ship. Wt.t5.98.110.213.116.717.922.429.8///////
Main shell shipping Wt.t2.444.75.25.96.98.111.613.416.117.821.923.829.241.5
Chiller operation Wt.t6.48.811.214.618.619.924.43337.547.859.274.486.3104.8114

General Conditions: ​

  1. Rated hot W. inlet / outlet temp. for hot W. chiller: 180°C/165°C.
  2. Rated exhaust inlet / outlet temp. for exhaust chiller: 500°C/160°C.
  3. Rated chilled W. outlet / inlet temp.: 7°C/14°C (or 7°C/12°C).
  4. Rated cooling W. outlet / inlet temp.: 37°C/30°C (or 37.5°C/32°C).
  5. Rated heating W. outlet / inlet temp. for two-stage exhaust chiller: 65°C/55°C.
  6. Lowest permitted outlet temp. for chilled water: 5°C.
  7. Lowest permitted inlet temp. for cooling water: 10°C.
  8. Adjustable chilled water flowrate: 50%~120%.
  9. Pressure limit for chilled / cooling water: 0.8MPa (except special order).
  10. Adjustable load: 5%~115%.
  11. Fouling factor for cooling W.: 0.044m² · K/kW, for chilled W. / heating W.: 0.018m² · K/kW.
  12. LiBr Solution concentration: 54%, solution is included in unit shipment Wt..
  13. Machine room ambient temperature: 5~43°C, humidity ≤85%.
  14. Rated cooling COP: 1.50 (including chiller power consumption), Rated heating COP for exhaust chiller: 0.93 (including chiller power consumption).
  15. Designed life: 60 years.
  16. Please refer to Performance Curves, Model Selection & Ordering & Supply List for performance curves, model selection & ordering and supply list information.