Packaged Steam Chiller Rated Parameters

Copy

Steam Chiller Rated Parameters (0.8/0.6/0.4MPa)

Steam from power generation or industrial waste streams

ModelBS203050751001251502002503004005006008001000
Cooling capacity
Cooling capacity (0.8/0.6)kW233349582872116314541745232629083489465258156978930411630
Cooling capacity (0.4)kW1822724546809071134136118142268272136294536544372579071
Chilled water
Flow rate (0.8/0.6)m³/h28.642.971.410714317921428635742957171485711431429
Flow rate (0.4)m³/h22.333.555.783.51121401672232783354455576688921115
Pressure dropkPa303030303040404050505060606060
Cooling water
Flow rate (0.8/0.6)m³/h47.571.21191782382973574765957149521189142719032379
Flow rate (0.4)m³/h3857.395.6143191239287382478573764955114615281910
Pressure dropkPa505050505050505080808090909090
Steam consumption
Steam consumption (0.8/0.6)kg/h234350586879117214651759234529323518469358647036938611732
Steam consumption (0.4)kg/h1982974957429901237148519792474296939584948593879179896
Other parameters
Power demandkW2.13.23.23.65.35.36.48.68.912.412.415.818.820.826.3
Solution wt.t0.71.21.92.22.63.33.556.47.39.41113.71720
Unit ship. wt.t4.15.87.2910.112.113.919.824.4//////
Main shell ship. wt.t2.444.75.25.96.98.111.613.416.117.621.923.829.241.5
Operation wt.t4.66.5810.312.114.316.723.228.834.14047.453.869.885
Copy

Packaged Steam Chiller Rated Parameters

Rated chilled water 7°C/14°C, cooling water 37°C/30°C

ModelBSY203050751001251502002503004005006008001000
Cooling capacity
Cooling capacitykW233349582872116314541745232629083489465258156978930411630
Pumpset
A/C W. pump
Pump headmH₂O222222242427272728282832323232
Power demandkW47.57.51515223037446060110110150180
Cooling W. pump
Pump headmH₂O101010151515151516161617171717
Power demandkW37.57.5151522223744446090110150180
Total power demandkW71515303044527488104120200220300360
Operation Wt.t0.50.70.83.33.33.63.76.36.67.28.85.9/8.66.1/8.86.1/9.89.6/9.8
Cooling tower
Power demandkW5.51111111515152237373755.5747492.5
Operation Wt.t2.54.55.15.97.614.314.31923.423.428.735.146.757.471.8
Electricity & water consumption
Total power demandkW14.629.229.244.650.364.373.4104.6133.9153.4169.4271.3313394.8478.8
W. demand for coolingt/h0.60.91.5233.84.567.591215182430

General Conditions: ​

  1. Rated saturated steam pressure: 0.8/0.6/0.4 MPa, condensate temp.: 95°C.
  2. Rated chilled W. outlet / inlet temp.: 7/14°C (or 7/12°C).
  3. Rated cooling W. outlet / inlet temp.: 37/30°C (or 38/32°C).
  4. Lowest permitted outlet temp. for chilled water: 5°C.
  5. Lowest permitted inlet temp. for cooling water: 10°C.
  6. Steam pressure upper limit 110%.
  7. Adjustable heating / hot water flowrate: 50%~120%.
  8. Pressure limit for chilled W., cooling W.: 0.8MPa (except special order).
  9. Adjustable load: 5%~115%.
  10. Fouling factor for cooling W.: 0.044 m²·K/kW, for chilled W.: 0.018 m²·K/kW.
  11. LiBr solution concentration: 52%. Solution is included in unit shipment Wt.
  12. Machine room ambient temperature: 5~43°C, humidity ≤ 85%.
  13. Standard climate conditions for cooling operation: 36°C, humidity 50% (wet bulb 27°C).
  14. Rated cooling COP (0.8/0.6): 1.50 (including chiller power consumption). Rated cooling COP (0.4): 1.40 (including chiller power consumption).
  15. Designed life: 60 years.