Packaged Single-stage Steam / Hot W. Chiller Rated Parameters

Copy

Packaged Single-stage Steam / Hot W. Chiller Rated Parameters

BDSY/BDHY: steam / hot water from power generation, solar panels or industrial waste streams (pumpset, enclosure data are the same as steam chiller)

Code / ModelUnit203050751001251502002503004005006008001000
BDS: Cooling capacity
Cooling capacitykW233349582872116314541745232629083489465258156978930411630
Heating capacitykW///////////////
BDS: Chilled W.
Chilled W. flow ratem³/h28.642.971.410714317921428635742957171485711431429
Chilled W. Pressure dropkPa303030303040404050506060606060
BDS: Cooling W.
Cooling W. flow ratem³/h64.696.916224232340448564780897012941617194025873234
Cooling W. Pressure dropkPa8585858585858585100100100100100120120
BDS: Steam consump- tion
Steam consump- tionkg/h45768711461718229228663440458657336881917311466137581834222935
BDS: Hot W. consump- tion
Hot W. consump- tionm³/h///////////////
BDS: Misc.
Power demandkW2.22.22.57.77.97.97.98.89.69.613.916.420.629.229.2
Solution Wt.t0.60.71.11.42.32.82.8455.66.510111315.3
Unit ship. Wt.t3.44.15.67.49.611.814.816.819.422.523.3/25.531.441.4
Main shell ship. Wt.t3.45.97.49.512.614.116.319.623.628.833.242.148.561.774.8
Chiller operation Wt.t3.45.97.49.512.614.116.319.623.628.833.242.148.561.774.8
BDH: Cooling capacity
Cooling capacitykW209302512767102312791535204625583069409251156138818410230
Heating capacitykW///////////////
BDH: Chilled W.
Chilled W. flow ratem³/h25.237.662.994.212515718825131337650362875410061256
Chilled W. Pressure dropkPa252525252530303030305050506060
BDH: Cooling W.
Cooling W. flow ratem³/h58.686.514521829136343658272787211631454174523262908
Cooling W. Pressure dropkPa75757575759090909090909090100100
BDH: Steam consump- tion
Steam consump- tionkg/h///////////////
BDH: Hot W. consump- tion
Hot W. consump- tionm³/h23.935.859.889.7119.6149.6179.6239.4299.2359.2478.8598.5718.1957.31197.1
BDH: Exhaust consumption
Exhaust Consaption (cooling)kg/h///////////////
Exhaust Consaption (heating)kg/h///////////////
BDH: Misc.
Power demandkW2.22.22.57.77.97.97.98.89.69.613.916.420.629.229.2
Solution Wt.t0.60.71.11.42.32.32.8455.66.510111315.3
Unit ship. Wt.t3.54.25.87.58.89.91217.219.622.823.823.926.631.441.4
Main shell ship. Wt.t3.76.17.99.811.213.314.520.524.630.835.545.452.265.980.8
Chiller operation Wt.t3.76.17.99.811.213.314.520.524.630.835.545.452.265.980.8

General Conditions: ​

  1. Rated saturated steam pressure for BDS chiller 0.1MPa, Rated condensate temperature for BDS chiller: 95°C.
  2. Rated hot W. inlet / outlet temp. for single-stage hot W. chiller: 98°C/88°C.
  3. Rated chilled W. outlet / inlet temp.: 7°C/14°C (or 7°C/12°C).
  4. Rated cooling W. outlet / inlet temp.: 37°C/30°C (or 37.5°C/32°C).
  5. Lowest permitted outlet temp. for chilled water: 5°C.
  6. Lowest permitted inlet temp. for cooling water: 10°C.
  7. Adjustable chilled water flowrate: 50%~120%.
  8. Pressure limit for chilled / cooling water: 0.8MPa (except special order).
  9. Adjustable load: 5%~115%.
  10. Fouling factor for cooling W.: 0.044m² · K/kW, for chilled W.: 0.018m² · K/kW.
  11. LiBr Solution concentration: 43%, solution is included in unit shipment Wt..
  12. Machine room ambient temperature: 5~43°C, humidity ≤ 85%.
  13. Rated cooling COP for single-stage steam chiller: 0.79 (including chiller power consumption), Rated cooling COP for single-stage hot W. chiller: 0.76 (including chiller power consumption).
  14. Designed lifespan: 60 years.
  15. Please refer to Performance Curves, Model Selection & Ordering & Supply List for performance curves, model selection & ordering and supply list information.