Packaged Multi-energy Chiller Rated Parameters

Copy

Packaged Multi-energy Chiller Rated Parameters

BZEY/BHEY/BZHEY: gas (oil) and waste heat hybrid (multi-energy chiller) (pumpset, enclosure data are the same as DFA)

Code / ModelUnit203050751001251502002503004005006008001000
BZE: Cooling / Heating capacity
Cooling capacitykW233349582872116314541745232629083489465258156978930411630
Heating capacitykW1792694496728971121134917912245268735824489538571768967
BZE: Chilled W.
Chilled W. flow ratem³/h28.642.971.410714317921428635742957171485711431429
Chilled W. Pressure dropkPa303030303040404050506060606060
BZE: Heating W.
Heating W. flow ratem³/h15.323.138.557.977.196.4116153193231308385463617771
Heating W. Pressure dropkPa202020202020203030404050506060
BZE: Hot W.
Hot W. flow ratem³/h3.45.28.612.917.221.525.834.44351.668.885.9///
Hot W. Pressure dropkPa202020202020203030404050///
BZE: Cooling W.
Cooling W. flow ratem³/h47.571.21191782382973574765957149521189142719032379
Cooling W. Pressure dropkPa505050505050505080808090909090
BZE: Misc.
Power demandkW2.33.53.95.16.88.89.916.316.622.426.629.339.349.753.3
Solution Wt.t1.42.12.73.74.85.57.4910.5131620.32629.534
BHE: Cooling / Heating capacity
Cooling capacitykW233349582872116314541745232629083489465258156978930411630
Heating capacitykW179269384575767959115115341918230130683835460261377671
BHE: Chilled W.
Chilled W. flow ratem³/h28.642.971.410714317921428635742957171485711431429
Chilled W. Pressure dropkPa303030303040404050506060606060
BHE: Heating W.
Heating W. flow ratem³/h11.619.629.343.858.47388.2117146175233293351467584
Heating W. Pressure dropkPa152015151515152525353545455555
BHE: Hot W.
Hot W. flow ratem³/h3.45.28.612.917.221.525.834.44351.668.885.9///
Hot W. Pressure dropkPa202020202020203030404050///
BHE: Cooling W.
Cooling W. flow ratem³/h52.573.313119626232739352565578710491311157320972622
Cooling W. Pressure dropkPa505050505050606080808090909090
BHE: Misc.
Power demandkW2.13.23.65.15.35.36.48.68.912.412.415.818.820.826.3
Solution Wt.t1.222.63.74.35.36.98.49.812.41620.125.62933
BZHE: Cooling / Heating capacity
Cooling capacitykW233349582872116314541745232629083489465258156978930411630
Heating capacitykW1792694496728971121134917912245268735824489538571768967
BZHE: Chilled W.
Chilled W. flow ratem³/h28.642.971.410714317921428635742957171485711431429
Chilled W. Pressure dropkPa303030303040404050506060606060
BZHE: Heating W.
Heating W. flow ratem³/h15.323.138.557.977.196.4116153193231308385463617771
Heating W. Pressure dropkPa202020202020203030404050506060
BZHE: Hot W.
Hot W. flow ratem³/h3.45.28.612.917.221.525.834.44351.668.885.9///
Hot W. Pressure dropkPa202020202020203030404050///
BZHE: Cooling W.
Cooling W. flow ratem³/h52.578.713119626232739352565578710491311157320972622
Cooling W. Pressure dropkPa505050505050606080808090909090
BZHE: Misc.
Power demandkW2.33.63.95.16.88.89.916.316.622.426.629.339.349.753.3
Solution Wt.t1.82.6344.86.57.491214.216.8222831.537
Copy

Energy consumption

Cooling / Heating / Hot water energy consumption and weights

Cooling NG Nm³/hCooling Exhaust kg/hCooling Hot water m³/hHeating NG Nm³/hHeating Exhaust kg/hHot water NG Nm³/hHot water Exhaust kg/hUnit ship. Wt. tMain shell Wt. tOperation Wt. t
16.24326.619.24598.54595.62.46
24.36479.928.868712.86878.43.48.9
40.7108216.448.1114621.4114610.44.710.9
61.1162424.771.9171732171713.55.214.7
81.4216432.996.1229142.7229116.95.918.8
102270741120286653.5286619.56.920.7
122325049.3144343464343423.18.125.4
163435259.2192459085459029.711.632.6
204541782.22415711107571131.412.338.4
244649998.72886867128686716.114.346.4
32686711323849179171917917.615.656.2
40710834164481114572071145721.919.167.1
48913000197577138042321380423.821.881
65217340263769183242631832429.230.3103.8
81521674329961229133292291341.531.4116.2

General Conditions: ​

  1. Rated chilled W. outlet / inlet temp. : 7°C/14°C (or 7°C/12°C).
  2. Rated cooling W. outlet / inlet temp. : 37°C/30°C (or 37.5°C/32°C).
  3. Rated heating W. outlet / inlet temp. : 65°C/55°C.
  4. Rated hot W. outlet / inlet temp. : 80°C/60°C.
  5. Lowest permitted outlet temp. for chilled water: 5°C.
  6. Highest permitted outlet temp. for heating / hot water: 95°C.
  7. Lowest permitted inlet temp. for cooling water: 10°C.
  8. Adjustable chilled water flowrate: 50%~120%.
  9. Adjustable heating / hot water flowrate: 65%~120%.
  10. Pressure limit for chilled W., cooling W., heating W., hot W. 0.8MPa (except special order).
  11. Adjustable load: 5%~115%.
  12. Fouling factor for cooling W. : 0.044m² · K/kW, for chilled W. / heating W./ hot W.: 0.018m² · K/kW.
  13. LiBr Solution concentration: 54%. Solution is included in unit shipment Wt..
  14. Natural gas consumption is calculated: 10kWh/Nm³ (8600kcal/Nm³).
  15. Standard natural gas dynamic pressure is 16~35kPa. Static pressure is <50kPa, lower or higher pressure can be accommodated to special orders.
  16. Machine room ambient temperature: 5~43°C, humidity ≤85%.
  17. Standard climate conditions for cooling operation: 36°C, humidity 50% (wet bulb 27°C).
  18. Exhaust provides 30% of the total capacity of chiller by standard design of BZE/ BZHE. Over 30% can be accommodated into special orders.
  19. Energy consumption is for separate operation of heat source and fuel.
  20. Designed lifespan: 60 years.
  21. Please refer to [Performance Curves](performance-curves), [Model Selection & Ordering](model-selection-ordering) & [Supply List](supply-list) for performance curves, model selection & ordering and supply list information.