Model Selection Curves
Model Selection Curves
Chilled/cooling water temp., cooling capacity, COP.
BZ
The figure in blue is COP. In calculation, 3 COP values are added up and then divided by 3. e.g.
1. Cooling capacity is 100%, cooling water temp. is 28°C, then chilled water temp. is 6.2°C, COP is 1.419; i.e. (1.42 + 1.44 + 1.419) / 3 = 1.419.
2. Chilled water temp. is 10°C, cooling water temp. is 30°C, then cooling capacity is 116%, COP = 1.435.
3. Cooling capacity is 90%, chilled water is 6°C , then cooling water temp. is 30°C, COP = 1.413.
BH
BS
The figure in blue is COP. In calculation, 4 COP values are added up and then divided by 4. e.g.
1. Cooling capacity is 90%, steam pressure 0.8 MPa, chilled water temp. is 6°C, then cooling water temp. is 30.5°C, COP = 1.488; (1.505 + 1.5 + 1.45 +1.498) / 4 = 1.488.
2. Steam pressure 0.7 MPa, chilled water temp. is 8°C, cooling water temp. is 28°C, then cooling capacity is 106%, COP = 1.496.
3. Cooling capacity is 90%, steam pressure 0.5 MPa, cooling water temp. is 30°C, then chilled water temp. is 7°C, COP is 1.451.
BE
BDH
BDS
The figure in blue is COP (BH, BE, BDH, BDE, BDS).
Calculation is the same as BZ & BS models.