Direct-fired Heater Rated Parameters

Copy

Direct-fired Heater Rated Parameters

ModelBZR162440608010012016020024032040050060080010001200
Heating capacity
Heating capacitykW18628046569893011631396186123262791372246505815697893041163013956
Hot W. capacitykW80120200300400500600800100012001600200025003000400050006000
Heating water
Flow ratem³/h162440608010012016020024032040050060080010001200
Pressure dropkPa2525252525252535354545555560607070
Hot water
Flow ratem³/h3.45.28.612.917.221.525.834.443546486108129172215258
Pressuer dropkPa2020202020202030304040505060608080
NG consumption
Heating waterNm³/h19.829.849.5749912414919824729739649561974299012371485
Hot waterNm³/h8.512.821.33243536485106128170213266319426532638
Power demand
Power demandkW0.40.41.51.52.72.74.66.67.69.112.115.130.530.537.555.575.5
Solution Wt.t0.50.60.91.21.31.51.722.52.83.54.26.88101218
Ship Wt.t1.82.83.3455.86.68.910.511.814.817.218.522283340
Operation Wt.t23.13.64.55.66.47.39.711.312.715.718.219232934.542
Copy

Packaged Direct-fired Heater

Rated heating water temp. 65/55°C, hot water 80/60°C

ModelBZRY162440608010012016020024032040050060080010001200
Pump headmH₂O2122222222242427272728282830323232
Power demandkW2.234447.57.5111518.522303037557575
Pump headmH₂O1515151515151515151515151515151515
Power demandkW1.11.11.51.11.51.52.22.22.233445.57.57.57.5
Total power demand kWkW3.34.15.510.2111819.426.434.44350686885125165165

General Conditions: ​

  1. Rated heating W. outlet / inlet temp.: 65°C/55°C.
  2. Rated hot W. outlet / inlet temp.: 80°C/60°C.
  3. Highest permitted outlet temp. for heating / hot water: 90°C.
  4. Adjustable heating / hot water flowrate: 65%~120%.
  5. Pressure limit for heating W., hot W.: 0.8MPa (except special order).
  6. Adjustable load: 5%~115%.
  7. Fouling factor for heating W., hot W., heating W.: 0.018m²·K/kW.
  8. Solution Wt. means a special antiseptic and antifreeze solution; if cooling function needed, it will be LiBr solution with 40% concentration.
  9. Natural gas consumption is calculated: 10kWh/ Nm³ (8600kcal/Nm³).
  10. Standard natural gas dynamic pressure is 16~35kPa, static pressure is < 50kPa, lower or higher pressure can be accommodated to special orders.
  11. Rated exhaust temp. 125°C.
  12. Machine room ambient temperature: 5~43°C, humidity ≤ 85%.
  13. The performance data of heating W. and hot W. in the table show two running conditions respectively, and both of them can be adjusted within the range.
  14. Rated heating COP: 0.94 (including chiller power consumption).
  15. Designed lifespan: 60 years.