Condensing Heat Recovery Chiller Rated Parameters

Copy

Condensing Heat Recovery Chiller Rated Parameters

ModelBZ203050751001251502002503004005006008001000
Condensing Heat Recovery Condition
Cooling capacitykW233349582872116314541745232629083489465258156978930411630
10⁴kcal/h203050751001251502002503004005006008001000
Hot W. capacitykW801202003004005006008001000120016002000240032004000
Chilled water
Flowratem³/h28.64371.410714317921428635742957171485711431429
Pressure dropkPa303030303040404050506060606060
Hot water
Flowratem³/h3.45.28.612.917.221.525.834.44351.56986103138172
Pressure dropkPa202020202020203030404040505050
Cooling water
Flowratem³/h44.266.21101652202753304405506608801100132017602199
Pressure dropkPa505050505050505060606060606060
NG consumption
CoolingNm³/h12.618.931.44762.678.394125156188250313376501625
Hot waterNm³/h8.512.821.43242.753.56485107128171214256342428
Heating Condition
Heating capacitykW1792694496728971121134917912245268735824489538571768967
10⁴kcal/h15.32338.557.977.196.4116154193231308386463617771
Heating water
Flowratem³/h15.323.138.557.977.196.4116153193231308385463617771
Pressure dropkPa202020202020203030404050506060
NG consumptionNm³/h1928.747.97295.9120144190240287383479576767959
Power demand
Power demandkW2.33.83.95.16.88.89.916.316.622.426.629.339.349.753.3
Solution Wt.t11.62.32.83.84.35.66.88.510.312.616212532
Unit ship. Wt.t5.17.79.212.11516.920.126.331.5//////
Main shell ship. Wt.t2.444.75.25.96.98.111.613.416.117.621.923.829.241.5
Operation Wt.t5.78.31013.717.319.523.43034.942.651.16174.891.1110.2

The dimension is the same as DFA chiller.

General Conditions: ​

  1. Rated chilled W. outlet / inlet temp.: 7°C/14°C (or 7°C/12°C).
  2. Rated cooling W. outlet / inlet temp.: 37°C/30°C (or 37.5°C/32°C).
  3. Rated hot W. outlet / inlet temp.: 80°C/60°C.
  4. Rated heating W. outlet / inlet temp.: 65°C/55°C.
  5. Lowest permitted outlet temp. for chilled water: 5°C.
  6. Highest permitted outlet temp. for heating / hot water: 95°C.
  7. Lowest permitted inlet temp. for cooling water: 10°C.
  8. Adjustable chilled water flowrate: 50%~120%, Adjustable heating / hot water flowrate: 65%~120%.
  9. Pressure limit for chilled W., cooling W., heating W., hot W.: 0.8MPa (except special order).
  10. Adjustable load: 5%~115%.
  11. Fouling factor for cooling W.: 0.044m²·K/kW, for chilled W. / heating W. / hot W.: 0.018m²·K/kW.
  12. The NG consumption data under condensing heat recovery condition when chilled W. and hot W. working simultaneously.
  13. Natural gas consumption is calculated: 10kWh/Nm³ (8600kcal/Nm³).
  14. Standard natural gas dynamic pressure is 16~35kPa, static pressure is < 50kPa, lower or higher pressure can be accommodated by special orders.
  15. LiBr Solution concentration: 54%. Solution is included in unit shipment Wt..
  16. Machine room ambient temperature: 5~43°C, humidity ≤ 85%.
  17. Rated cooling COP: 1.85, Rated heating COP: 0.93 (including chiller power consumption).
  18. Designed lifespan: 60 years.