Direct Absorption Chiller — Rated Parameters

Copy

Direct-fired Absorption Chiller (DFA) Rated Parameters

Fuel: natural gas, town gas, biogas, diesel or gas/oil dual fuel

ModelBZ203050751001251502002503004005006008001000
Cooling capacity
kW233349582872116314541745232629083489465258156978930411630
10⁴kcal/h203050751001251502002503004005006008001000
RT669916524833141349666182799213231653198426453307
Heating capacity
kW1792694496728971121134517932242269035874483538071738967
Hot water capacity
kW80120200300400500600800100012001600////
Chilled water
Flow ratem³/h28.642.971.410714317921428635742957171485711431429
Pressure dropkPa303030303040404050506060606060
Cooling water
Flow ratem³/h47.571.21191782382973574765957149521190142719032380
Pressure dropkPa505050505050505080808090909090
Heating water
Flow ratem³/h15.323.138.557.977.196.4116153193231308385463617771
Pressure dropkPa202020202020203030404050506060
Hot water
Flow ratem³/h3.45.28.612.917.221.525.834.44351.668.8////
Pressure dropkPa2020202020202030304040////
NG consumption
CoolingNm³/h16.224.340.761.181.4102122163204244326407489652815
HeatingNm³/h1928.747.97295.9120144190240287383479576767959
Hot waterNm³/h8.512.821.43242.753.56485107128171////
Power demand
kW2.33.83.95.16.88.89.916.316.622.426.629.339.349.753.3
Weight
Solution wt.t11.62.32.83.84.35.66.88.510.312.616212532
Unit ship wt.t5.17.79.212.11516.920.126.331.5//////
Main shell ship. wt.t2.444.75.25.96.98.111.613.416.117.621.923.829.241.5
Operation wt.t5.78.31013.717.319.523.43034.942.651.16174.891.1110.2
Copy

Packaged Direct-fired Absorption Chiller (P-DFA)

Rated chilled water 7°C/14°C, cooling water 37°C/30°C

ModelBZY203050751001251502002503004005006008001000
Cooling capacity
kW233349582872116314541745232629083489465258156978930411630
Pumpset
Chilled water pump
Pump headmH₂O222222242427272728282832323232
Power demandkW47.57.51515223037446060110110150180
Cooling water pump
Pump headmH₂O101010151515151516161617171717
Power demandkW37.57.5151522223744446090110150180
Hot water pump
Pump headmH₂O7771515151515151515////
Power demandkW0.40.580.582.2334.44.44.466////
Total power demand kWkW7.415.615.632.2334756.478.492.4110126200220300360
Operation wt.t0.60.80.93.83.84.24.37.17.48.19.859/8.661/8.861/9.896/9.8
Cooling tower
Power demandkW5.51111////////////
Operation wt.t2.54.55.1////////////
Electricity & water consumption
Total power demand kWkW15.230.730.836.338.354.364.893.2107130.4150.6227.3256.3346.7410.3
Water demand for coolingt/h0.60.91.5233.84.567.591215182430
Copy

HTG (high temp. generator) Enlarged Model Rated Parameters

Enlarged ModelsHeating capacity kWGas Consumption m³/h
BZ 20
H121523
H225126.9
H328730.7
H432334.6
BZ 30
H132334.6
H237740.3
H343046.1
H448451.8
BZ 50
H153857.7
H262867.3
H371777
H480786
BZ 75
H180786
H2942101
H31076115
H41211129
BZ 100
H11076115
H21255135
H31435154
H41614173
BZ 125
H11345144
H21569168
H31793192
H42018216
BZ 150
H11614173
H21883202
H32152230
H42421259
BZ 200
H12152230
H22511269
H32869307
H43228346
BZ 250
H12690289
H23138337
H33587386
H44035434
BZ 300
H13228346
H23766403
H34304461
H44842518
BZ 400
H14304461
H25021538
H35739614
BZ 500
H15380577
H26277673

Heating capacity increases by 20% for each stage of HTG enlargement. No change with pumpset (excluding hot W. pump) and enclosure specs.

Special design is available if heating capacity is higher than above list.

General Conditions ​

  1. Rated chilled W. outlet / inlet temp. 7°C/14°C (or 7°C/12°C).
  2. Rated cooling W. outlet / inlet temp. 37°C/30°C (or 37.5°C/32°C).
  3. Rated heating W. outlet / inlet temp. 65°C/55°C.
  4. Rated hot W. outlet / inlet temp. 80°C/60°C.
  5. Lowest permitted outlet temp. for chilled water: 5°C.
  6. Highest permitted outlet temp. for heating / hot water: 95°C.
  7. Lowest permitted inlet temp. for cooling water: 10°C.
  8. Adjustable chilled water flowrate: 50%~120%, Adjustable heating / hot water flowrate: 65%~120%.
  9. Pressure limit for chilled W., cooling W., heating W., hot W.: 0.8MPa (except special order).
  10. Adjustable load: 5%~115%.
  11. Fouling factor for cooling W. 0.044m²·K/kW, for chilled W. / heating W. / hot W. 0.018m²·K/kW.
  12. Natural gas consumption is calculated: 10kWh/Nm³ (8600kcal/Nm³).
  13. Standard natural gas dynamic pressure is 16~35kPa, static pressure is < 50kPa; lower or higher pressure can be accommodated to special orders.
  14. LiBr solution concentration: 54%. Solution is included in unit shipment wt.
  15. Rated exhaust temp. for cooling: 160°C, Rated exhaust temp. for heating: 145°C.
  16. Machine room ambient temperature: 5~43°C, humidity ≤85%.
  17. Standard climate conditions for cooling operation: temp. 36°C, relative humidity 50% (wet bulb 27°C).