Direct Absorption Chiller — Rated Parameters
Copy
Direct-fired Absorption Chiller (DFA) Rated Parameters
Fuel: natural gas, town gas, biogas, diesel or gas/oil dual fuel
| Model | BZ | 20 | 30 | 50 | 75 | 100 | 125 | 150 | 200 | 250 | 300 | 400 | 500 | 600 | 800 | 1000 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Cooling capacity | ||||||||||||||||
| kW | 233 | 349 | 582 | 872 | 1163 | 1454 | 1745 | 2326 | 2908 | 3489 | 4652 | 5815 | 6978 | 9304 | 11630 | |
| 10⁴kcal/h | 20 | 30 | 50 | 75 | 100 | 125 | 150 | 200 | 250 | 300 | 400 | 500 | 600 | 800 | 1000 | |
| RT | 66 | 99 | 165 | 248 | 331 | 413 | 496 | 661 | 827 | 992 | 1323 | 1653 | 1984 | 2645 | 3307 | |
| Heating capacity | ||||||||||||||||
| kW | 179 | 269 | 449 | 672 | 897 | 1121 | 1345 | 1793 | 2242 | 2690 | 3587 | 4483 | 5380 | 7173 | 8967 | |
| Hot water capacity | ||||||||||||||||
| kW | 80 | 120 | 200 | 300 | 400 | 500 | 600 | 800 | 1000 | 1200 | 1600 | / | / | / | / | |
| Chilled water | ||||||||||||||||
| Flow rate | m³/h | 28.6 | 42.9 | 71.4 | 107 | 143 | 179 | 214 | 286 | 357 | 429 | 571 | 714 | 857 | 1143 | 1429 |
| Pressure drop | kPa | 30 | 30 | 30 | 30 | 30 | 40 | 40 | 40 | 50 | 50 | 60 | 60 | 60 | 60 | 60 |
| Cooling water | ||||||||||||||||
| Flow rate | m³/h | 47.5 | 71.2 | 119 | 178 | 238 | 297 | 357 | 476 | 595 | 714 | 952 | 1190 | 1427 | 1903 | 2380 |
| Pressure drop | kPa | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 80 | 80 | 80 | 90 | 90 | 90 | 90 |
| Heating water | ||||||||||||||||
| Flow rate | m³/h | 15.3 | 23.1 | 38.5 | 57.9 | 77.1 | 96.4 | 116 | 153 | 193 | 231 | 308 | 385 | 463 | 617 | 771 |
| Pressure drop | kPa | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 30 | 30 | 40 | 40 | 50 | 50 | 60 | 60 |
| Hot water | ||||||||||||||||
| Flow rate | m³/h | 3.4 | 5.2 | 8.6 | 12.9 | 17.2 | 21.5 | 25.8 | 34.4 | 43 | 51.6 | 68.8 | / | / | / | / |
| Pressure drop | kPa | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 30 | 30 | 40 | 40 | / | / | / | / |
| NG consumption | ||||||||||||||||
| Cooling | Nm³/h | 16.2 | 24.3 | 40.7 | 61.1 | 81.4 | 102 | 122 | 163 | 204 | 244 | 326 | 407 | 489 | 652 | 815 |
| Heating | Nm³/h | 19 | 28.7 | 47.9 | 72 | 95.9 | 120 | 144 | 190 | 240 | 287 | 383 | 479 | 576 | 767 | 959 |
| Hot water | Nm³/h | 8.5 | 12.8 | 21.4 | 32 | 42.7 | 53.5 | 64 | 85 | 107 | 128 | 171 | / | / | / | / |
| Power demand | ||||||||||||||||
| kW | 2.3 | 3.8 | 3.9 | 5.1 | 6.8 | 8.8 | 9.9 | 16.3 | 16.6 | 22.4 | 26.6 | 29.3 | 39.3 | 49.7 | 53.3 | |
| Weight | ||||||||||||||||
| Solution wt. | t | 1 | 1.6 | 2.3 | 2.8 | 3.8 | 4.3 | 5.6 | 6.8 | 8.5 | 10.3 | 12.6 | 16 | 21 | 25 | 32 |
| Unit ship wt. | t | 5.1 | 7.7 | 9.2 | 12.1 | 15 | 16.9 | 20.1 | 26.3 | 31.5 | / | / | / | / | / | / |
| Main shell ship. wt. | t | 2.4 | 4 | 4.7 | 5.2 | 5.9 | 6.9 | 8.1 | 11.6 | 13.4 | 16.1 | 17.6 | 21.9 | 23.8 | 29.2 | 41.5 |
| Operation wt. | t | 5.7 | 8.3 | 10 | 13.7 | 17.3 | 19.5 | 23.4 | 30 | 34.9 | 42.6 | 51.1 | 61 | 74.8 | 91.1 | 110.2 |
Copy
Packaged Direct-fired Absorption Chiller (P-DFA)
Rated chilled water 7°C/14°C, cooling water 37°C/30°C
| Model | BZY | 20 | 30 | 50 | 75 | 100 | 125 | 150 | 200 | 250 | 300 | 400 | 500 | 600 | 800 | 1000 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Cooling capacity | ||||||||||||||||
| kW | 233 | 349 | 582 | 872 | 1163 | 1454 | 1745 | 2326 | 2908 | 3489 | 4652 | 5815 | 6978 | 9304 | 11630 | |
| Pumpset | ||||||||||||||||
| Chilled water pump | ||||||||||||||||
| Pump head | mH₂O | 22 | 22 | 22 | 24 | 24 | 27 | 27 | 27 | 28 | 28 | 28 | 32 | 32 | 32 | 32 |
| Power demand | kW | 4 | 7.5 | 7.5 | 15 | 15 | 22 | 30 | 37 | 44 | 60 | 60 | 110 | 110 | 150 | 180 |
| Cooling water pump | ||||||||||||||||
| Pump head | mH₂O | 10 | 10 | 10 | 15 | 15 | 15 | 15 | 15 | 16 | 16 | 16 | 17 | 17 | 17 | 17 |
| Power demand | kW | 3 | 7.5 | 7.5 | 15 | 15 | 22 | 22 | 37 | 44 | 44 | 60 | 90 | 110 | 150 | 180 |
| Hot water pump | ||||||||||||||||
| Pump head | mH₂O | 7 | 7 | 7 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | / | / | / | / |
| Power demand | kW | 0.4 | 0.58 | 0.58 | 2.2 | 3 | 3 | 4.4 | 4.4 | 4.4 | 6 | 6 | / | / | / | / |
| Total power demand kW | kW | 7.4 | 15.6 | 15.6 | 32.2 | 33 | 47 | 56.4 | 78.4 | 92.4 | 110 | 126 | 200 | 220 | 300 | 360 |
| Operation wt. | t | 0.6 | 0.8 | 0.9 | 3.8 | 3.8 | 4.2 | 4.3 | 7.1 | 7.4 | 8.1 | 9.8 | 59/8.6 | 61/8.8 | 61/9.8 | 96/9.8 |
| Cooling tower | ||||||||||||||||
| Power demand | kW | 5.5 | 11 | 11 | / | / | / | / | / | / | / | / | / | / | / | / |
| Operation wt. | t | 2.5 | 4.5 | 5.1 | / | / | / | / | / | / | / | / | / | / | / | / |
| Electricity & water consumption | ||||||||||||||||
| Total power demand kW | kW | 15.2 | 30.7 | 30.8 | 36.3 | 38.3 | 54.3 | 64.8 | 93.2 | 107 | 130.4 | 150.6 | 227.3 | 256.3 | 346.7 | 410.3 |
| Water demand for cooling | t/h | 0.6 | 0.9 | 1.5 | 2 | 3 | 3.8 | 4.5 | 6 | 7.5 | 9 | 12 | 15 | 18 | 24 | 30 |
Copy
HTG (high temp. generator) Enlarged Model Rated Parameters
| Enlarged Models | Heating capacity kW | Gas Consumption m³/h |
|---|---|---|
| BZ 20 | ||
| H1 | 215 | 23 |
| H2 | 251 | 26.9 |
| H3 | 287 | 30.7 |
| H4 | 323 | 34.6 |
| BZ 30 | ||
| H1 | 323 | 34.6 |
| H2 | 377 | 40.3 |
| H3 | 430 | 46.1 |
| H4 | 484 | 51.8 |
| BZ 50 | ||
| H1 | 538 | 57.7 |
| H2 | 628 | 67.3 |
| H3 | 717 | 77 |
| H4 | 807 | 86 |
| BZ 75 | ||
| H1 | 807 | 86 |
| H2 | 942 | 101 |
| H3 | 1076 | 115 |
| H4 | 1211 | 129 |
| BZ 100 | ||
| H1 | 1076 | 115 |
| H2 | 1255 | 135 |
| H3 | 1435 | 154 |
| H4 | 1614 | 173 |
| BZ 125 | ||
| H1 | 1345 | 144 |
| H2 | 1569 | 168 |
| H3 | 1793 | 192 |
| H4 | 2018 | 216 |
| BZ 150 | ||
| H1 | 1614 | 173 |
| H2 | 1883 | 202 |
| H3 | 2152 | 230 |
| H4 | 2421 | 259 |
| BZ 200 | ||
| H1 | 2152 | 230 |
| H2 | 2511 | 269 |
| H3 | 2869 | 307 |
| H4 | 3228 | 346 |
| BZ 250 | ||
| H1 | 2690 | 289 |
| H2 | 3138 | 337 |
| H3 | 3587 | 386 |
| H4 | 4035 | 434 |
| BZ 300 | ||
| H1 | 3228 | 346 |
| H2 | 3766 | 403 |
| H3 | 4304 | 461 |
| H4 | 4842 | 518 |
| BZ 400 | ||
| H1 | 4304 | 461 |
| H2 | 5021 | 538 |
| H3 | 5739 | 614 |
| BZ 500 | ||
| H1 | 5380 | 577 |
| H2 | 6277 | 673 |
Heating capacity increases by 20% for each stage of HTG enlargement. No change with pumpset (excluding hot W. pump) and enclosure specs.
Special design is available if heating capacity is higher than above list.
General Conditions
- Rated chilled W. outlet / inlet temp. 7°C/14°C (or 7°C/12°C).
- Rated cooling W. outlet / inlet temp. 37°C/30°C (or 37.5°C/32°C).
- Rated heating W. outlet / inlet temp. 65°C/55°C.
- Rated hot W. outlet / inlet temp. 80°C/60°C.
- Lowest permitted outlet temp. for chilled water: 5°C.
- Highest permitted outlet temp. for heating / hot water: 95°C.
- Lowest permitted inlet temp. for cooling water: 10°C.
- Adjustable chilled water flowrate: 50%~120%, Adjustable heating / hot water flowrate: 65%~120%.
- Pressure limit for chilled W., cooling W., heating W., hot W.: 0.8MPa (except special order).
- Adjustable load: 5%~115%.
- Fouling factor for cooling W. 0.044m²·K/kW, for chilled W. / heating W. / hot W. 0.018m²·K/kW.
- Natural gas consumption is calculated: 10kWh/Nm³ (8600kcal/Nm³).
- Standard natural gas dynamic pressure is 16~35kPa, static pressure is < 50kPa; lower or higher pressure can be accommodated to special orders.
- LiBr solution concentration: 54%. Solution is included in unit shipment wt.
- Rated exhaust temp. for cooling: 160°C, Rated exhaust temp. for heating: 145°C.
- Machine room ambient temperature: 5~43°C, humidity ≤85%.
- Standard climate conditions for cooling operation: temp. 36°C, relative humidity 50% (wet bulb 27°C).