Energy Saving Comparison

Compared with conventional machine room layout, BROAD packaged pumpset system reduces the rated power demand by 50~70%, and the operating electricity consumption by 70~85% (the electricity for pumpset only amounts to 2~5% of the rated cooling capacity).

Examples on power consumption comparison ​

Copy

BY50 (pumpset for 582kW / 165Rt chillers)

Power consuming partsConventional machine room power demandPackaged pumpset power demandOperating power consumption
Cooling water pump30 kW7.5 kW2~7.5 kW
Cooling tower fan11 kW11 kW3~11 kW
Chilled/heating water pump22 kW7.5 kW7.5 kW
Total electricity/cooling capacity63 kW (10.8%)26 kW (4.47%)17 kW (annual, 2.92%)
Annual operating consumption190 MWh52 MWh (power saving is 79%)
Copy

BY300 (pumpset for 3489kW/992Rt chillers)

Power consuming partsConventional machine room power demandPackaged pumpset power demandOperating power consumption
Cooling water pump180 kW44 kW11~44 kW
Cooling tower fan37 kW37 kW6~37 kW
Chilled/heating water pump110 kW60 kW30~60 kW
Total electricity/cooling capacity327 kW (9.4%)141 kW (4.04%)100 kW (annual, 2.86%)
Annual operating consumption1000 MWh300 MWh (power saving is 76%)
Copy

BY1000 (pumpset for 11630kW/3307Rt chillers)

Power consuming partsConventional machine room power demandPackaged pumpset power demandOperating power consumption
Cooling water pump550 kW180 kW30~180 kW
Cooling tower fan110 kW110 kW20~110 kW
Chilled/heating water pump440 kW180 kW90~180 kW
Total electricity/cooling capacity1100 kW (9.5%)470 kW (4.04%)250 kW (annual, 2.15%)
Annual operating consumption3300 MWh750 MWh (power saving is 82%)

Why electricity saving ? ​

Saving from design: ​

  • Many innovations reduce the resistance from filters, valves and piping to almost zero.
  • Specially designed pumps optimize head and flow rate.

Saving from operation: ​

  • BROAD leads the world in inverter control system design and operation. Standard designs incorporate inverter-controlled cooling water pump(s) and cooling tower fan(s) which are automatically adjusted according to load and ambient temperature.
  • Two pumps combined or separate operation by software analyzer.
  • Actual power consumption during operation is 30~50% of the rated design.